Siwenoid Wiki

Intrusion view

The intrusion views: the areas and zones of the intrusion panels in one place, their states, sorting and filtering, and arming commands.

The intrusion view lists the areas (partitions) and zones of the intrusion (burglar alarm) panels in one place, with their current state. From the list you can find a zone on the map or in the tree and send commands such as arm, disarm or reset. Without it the same information is found panel by panel in the datapoint hierarchy.

The view shows the intrusion systems connected to Siwenoid, such as Aritech SPC, Galaxy, Paradox, Satel, DSC, Texecom, Sintony and the intrusion part of Cerberus CC440. You see only the panels your administrator allows you to see.

Opening the view

  1. Click + at the end of a tab pane.
  2. Choose Intrusion, then one of:
Entry Shows
Area states the areas only
Zone states the zones only
Area & Zone states areas and zones side by side

If you do not see Intrusion in the menu, your administrator has not given you access to it, or the intrusion view is not switched on for this workstation.

The Intrusion submenu of the + menu.
The Intrusion submenu of the + menu.

A pinned intrusion tab comes back at the next login.

The parts of the view

The view has up to three columns. Drag the dividers to resize them.

Column Content
Containers (left) The intrusion panels with their areas and zones, each with a check box.
Areas A card for each ticked area.
Zones A card for each ticked zone. Open a zone card to see the datapoints under it (up to three levels).

Nothing is ticked when the view opens: the right side says Select one or more Container(s) to show. Tick a panel to show all its areas and zones, or tick single areas and zones. If there is no intrusion panel you may see, the left side says No selectable container is found.

The cards follow the panels live: a change of state shows at once, and the list of panels is reloaded when panels are added or removed.

Area & Zone states with a panel ticked, a zone in alarm, and armed and disarmed areas.
Area & Zone states with a panel ticked, a zone in alarm, and armed and disarmed areas.

A card

Each card is one area or zone. From left to right:

Part Meaning
State square Filled with the colour of the highest-ranked status of the area or zone and of everything below it (the same colour as on the map and in the tree). Empty with a grey border when normal. A status whose device has returned to normal, but which has not been dealt with yet, fades through black. Hold the mouse over it to see the treatment's name (REMOVED is added for such a status); State when there is none.
Icon and name Click the name (tooltip Show in Physical Hierarchy) to select the datapoint in the Datapoint Hierarchy tab.
Technical text In brackets after the name.
Physical container The panel the area or zone belongs to.
Map buttons One small map icon for each map the datapoint is on; the tooltip names the map. Click it to open the map with the datapoint highlighted (see Maps).
Commands icon Appears at the right end while the mouse is over the card.

Acknowledging is not done here: acknowledge alarms in the signal log.

Sending commands

  1. Move the mouse over the card. The Commands icon appears at its right end.
  2. Click it. A menu opens with the name of the area or zone in bold and its commands.
  3. Choose the command, for example arm, disarm or reset. It is sent at once.
  4. If the command needs a passcode, enter your 4-digit passcode in the Passcode required window.
  5. Watch the state square: its colour changes when the panel reports the new state.

The commands are those the panel offers for that area or zone type; their names come from the panel's configuration. Failures are reported as in the datapoint hierarchy (see Datapoint hierarchy), and every command is written to the event log. A disabled or locked datapoint offers commands to administrators only. If no commands icon appears, your administrator has not given you access to sending commands.

The commands menu of an area card.
The commands menu of an area card.

Sorting and filtering

The header of the Areas and Zones columns has its own sort and filter:

Control Choices
Sort: Name (default), Category (the highest category first, so the cards in alarm are on top), Technical text
Category filter A list of the categories present, each with its icon. Tick one or more to show only the cards in those categories; the button shows the number ticked, for example Category filter (2). Clear filter removes it.

Sorting and filtering are not saved: they apply until the tab is closed.

The Sort list and the Category filter of the Zones column.
The Sort list and the Category filter of the Zones column.

Typical tasks

Checking which areas are armed

  1. Open + › Intrusion › Area states.
  2. Tick every panel in Containers.
  3. Set Sort: to Category. Areas in alarm come first; the colour of each state square shows whether the area is armed or disarmed.

Handling an intrusion alarm

  1. Open + › Intrusion › Area & Zone states and tick the panel.
  2. Set Sort: to Category in the Zones column. The zone in alarm is on top. Hold the mouse over its state square to read the treatment.
  3. Click its map button to see where it is, or its name to find it in the tree.
  4. Acknowledge the alarm in the signal log.
  5. When the cause is cleared, reset or re-arm the area with its commands icon.

A zone card opened to show the datapoints under it.
A zone card opened to show the datapoints under it.