Texecom Premier and Premier Elite

Connecting Texecom Premier and Premier Elite intrusion panels through a Com-IP module: choosing the handler type, Wintex settings, container parameters, importing the Wintex printout, commands.

At a glance
Manufacturer Texecom
Panels Premier 412, 816, 832
Premier 48, 88, 168, 640
Premier Elite 12, 24, 48, 88, 168, 640
Connection Simple Protocol over TCP, through the Com-IP module
Handler type see the table
Datapoints metafile import
Import Wintex printout (.xps, .oxps)

Texecom Premier and Premier Elite are intrusion alarm panels. Siwenoid connects over TCP to the Com-IP module of the panel and talks to it with Texecom's Simple Protocol. Siwenoid polls the state of the panel, its areas and zones. The zones and areas come from a printout of the panel programming made in Wintex, Texecom's programming software. Areas and zones can be controlled from the datapoint hierarchy, from maps and from the intrusion view.

Choosing the handler type

Siwenoid has three handler types for Texecom panels. They work the same way; choose the one that matches the panel model. Each has a single protocol.

Panel Handler type Protocol
Premier 412, 816, 832 Texecom Premier 412/816/832 Texecom Premier 412/816/832 Simple Protocol
Premier 48, 88, 168, 640 Texecom Premier 48/88/168/640 Texecom Premier 48/88/168/640 Simple Protocol
Premier Elite 12, 24, 48, 88, 168, 640 Texecom Elite 12/24/48/88/168/640 Texecom Elite 12/24/48/88/168/640 Simple Protocol

Preparing the panel in Wintex

Use Wintex 5.6 or newer, in English or Hungarian. The import reads the headings of the printout in these two languages only. The language is set in Wintex under Setup › Language; it changes after a restart of Wintex.

  1. Connect the programming cable (Premier Elite USB-Com) to the PC and to the COM1 connector of the panel's main board. In Windows, find the virtual COM port of the cable: Devices and Printers › FT232R USB UART › Properties › Hardware.

    The programming cable on COM1.
    The programming cable on COM1.

  2. In Wintex, add a new account and choose the panel model. Choose the newest software version; when you connect, Wintex tells you if another one is needed.

  3. Under Setup, choose the COM port of the cable. Connect with Connect using PC-COM, and receive the panel's programming.

  4. Open Comms, and set:

    • UDL Passcode: 4 to 8 digits. Siwenoid logs in with this code.
    • the COM port of the Com-IP module: set the port the module is connected to (for example Com Port 2) to Com-IP module,
    • Local IP Address: a free address on the subnet. Siwenoid connects to this address.
    • Local IP Port: a port number between 1 and 65535 (10001 is recommended). Siwenoid connects to this port.
    • Gateway and Subnet mask of the network.

    The Comms settings with the Com-IP module.
    The Comms settings with the Com-IP module.

  5. Send the configuration to the panel.

Tip

If Wintex does not send the UDL passcode or the Com-IP settings correctly, set them on the panel's keypad in the engineer menu (UDL and communication options: the COM port of the Com-IP module, the module's IP settings, the UDL code). A UDL passcode that differs between the keypad and the Wintex account may not be changed by a download: set it on the keypad.

Making the metafile

The metafile is a printout of the zone programming, saved as an XPS file.

  1. In Wintex choose Accounts › Print Account and Panel Details....

    Printing the account and panel details.
    Printing the account and panel details.

  2. Untick everything except Zone Programming, then press Print.

    Only the zone programming is printed.
    Only the zone programming is printed.

  3. Choose Microsoft XPS Document Writer as the printer, press OK, and save the file.

    Printing to an XPS file.
    Printing to an XPS file.

Important

Siwenoid imports only XPS or OXPS files, so the computer running Wintex needs an XPS printer. If Microsoft XPS Document Writer is not among the printers, this Windows feature is not installed. Install it in the Control Panel's Turn Windows features on or off window: tick Microsoft XPS Document Writer, then press OK.

Creating the container

Create the container in Preferences › Physical structure (see Physical structure for the editor in general). Give it a name, choose the Handler type from the table above and its Protocol, then fill in the connection parameters. All three are required.

The container editor with the Texecom connection parameters.
The container editor with the Texecom connection parameters.

Field Meaning Default
Host IP The Local IP Address set in Wintex: the address of the Com-IP module.
Port The Local IP Port set in Wintex.
UDL password The UDL Passcode of the panel.

Save the container and switch its connection on.

Importing the metafile

  1. On the container's page, press Import metafile.
  2. Press Open, and choose the XPS file (file types XML Paper Specification (Microsoft) and Open XML Paper Specification).
  3. Press Save. This handler has no import preview: when Siwenoid asks whether to import anyway, confirm.

Importing the Wintex printout.
Importing the Wintex printout.

The import creates the panel datapoint, named after the panel model, and two folders under it:

Importing the printout again updates the names by area and zone number.

Important

Siwenoid watches the zones that exist as datapoints, and reads their list when the connection starts. After an import, switch the container's connection off and on again.

Treatments and commands

The treatment files of the three handler types come with the handlers, in the TreatmentTables folder of the Siwenoid server, and the server loads them by itself at its first start. Before you switch on the first container, check in Preferences › Datapoint types that the datapoint types of the handler type have treatments. If they have none, or you received an updated treatment file, import the file of the handler type by hand (see Importing a treatment file); without treatments the panel's signals do not appear and there are no commands:

The commands are the same for the three handlers:

Datapoint Commands
Area ARM PARTITIONS (AREAS), PART ARM PARTITIONS (AREAS), DISARM PARTITIONS (AREAS), RESET PARTITIONS (AREAS)
Zone BYPASS (OMIT) ZONES, UNBYPASS (REINSTATE) ZONES

Checking the connection

  1. The panel datapoint shows connected in the datapoint hierarchy.
  2. Open a zone, and check that its state changes in Siwenoid.
  3. If nothing arrives:
    • check these fields against the Wintex settings and the keypad:
      • Host IP,
      • Port,
      • UDL password,
    • check that the handler type matches the panel model,
    • check that the datapoint types of the handler type have treatments (Preferences › Datapoint types),
    • check that the metafile is imported, and switch the connection off and on again.