Physical structure
Containers and their connection parameters, switching the communication on and off, metafile import with preview, datapoint browsing, the datapoint editor, CCTV assignments and restarting the communication.
| At a glance | |
|---|---|
| Where | File › Settings › Physical structure |
| View permission | Manage physical hierarchy |
| Container | one connected subsystem (panel, network, recorder) |
| Datapoints | imported, browsed or added by hand |
The physical structure is where the connected subsystems are set up. Each fire panel, intrusion panel, BACnet network, camera recorder or I/O module is a container: it has a handler type, a protocol and the connection parameters, and it holds the datapoints of that device (zones, detectors, inputs, outputs, cameras...) in the device's own structure.
This page describes the screen in general. The parameters and import files of each device are on the subsystem pages (see Supported subsystems).
Concepts
- Physical container: one connection to one subsystem. Its datapoints form a tree under it, as the device organises them. The operators see the same datapoints in the datapoint hierarchy, where they can be regrouped into logical containers. The physical structure always shows the original structure.
- System container: always exists and is always the first row of the list. It holds the datapoints of the Siwenoid servers, the clients and the database. It cannot be deleted and its communication cannot be switched off.
- Device: some containers hold more than one device (for example networked panels). Each device is a datapoint under the container, with the device's datapoints below it.
- Original name and chosen name: a datapoint gets its original name from the import or from the device. You can give it another name in the datapoint editor; clearing that name restores the original one.
The screen
Open File › Settings › Physical structure.

The physical structure screen: the container list on the left, the selected container's tree and its editor on the right.
Left: Physical Containers. One row per container: its name, its handler type and the time its datapoints were last imported or browsed (Last updated at ...). A container whose datapoints were never loaded from the device shows Never imported / browsed. Above the list:
- + adds a new container, - deletes the selected one (both appear only for users who may add and remove containers; - is disabled for the System container),
- the sort button (tooltip Order) orders the list by Name (A–Z), Name (Z–A), Handler type or Last updated. The System container stays first in every order.
Right: the datapoint tree and the editor. The selected container's datapoints are shown as a tree, loaded level by level as you expand it. Next to the tree an editor opens for the selection:
| You select | Editor |
|---|---|
| The container's own row (the top of the tree) | Container editor |
| One datapoint | Datapoint editor |
| Several datapoints (Ctrl or Shift click) | Multi-selection editor |
Right-click a row of the tree for more functions (see The datapoint tree and its context menu below).
The list and the tree follow the changes made on other clients.
The container editor
The editor's title is the container's name, or New container for one that was not saved yet.
General
| Field | Meaning |
|---|---|
| Name | The container's name, shown in the trees, the signal log and the event log. Required. |
| Handler type | The subsystem family (the handlers installed on the server). It cannot be changed once the container has been saved with a protocol. |
| Protocol | The protocol of the chosen handler. Choosing it builds the Connection section. Required. |
| Map label | Which text is shown as the caption next to this container's datapoint icons on the maps: Technical text (default) or Name. Some panels identify their points by loop and address (technical text), others carry the meaningful description in the name. The caption itself is switched on per map. Available after the container was saved once; it takes effect when a map is next opened. |
Switching the communication On and Off
The On / Off switch next to the name controls whether Siwenoid communicates with the device. With Off no messages arrive from the device and no commands can be sent to it.
- Switching On checks the licence. If the datapoints would exceed it, the warning The number of datapoints exceeds the licence. appears and the container stays off (see Licensing).
- The switch is not available for the System container and for a container that was not saved yet.
- A container that is switched off cannot be browsed and its communication cannot be restarted.
Connection
The Connection section lists the parameters of the chosen protocol, such as the device's IP address and port. A protocol without parameters has no such section. The parameters of each device are on its subsystem page.
| Input | How to fill it in |
|---|---|
| Text | Free text. |
| Password | Masked. A stored password is never shown: the empty field reads Stored, leave empty to keep it. Leave it empty to keep the stored value, type a new one to replace it. |
| Number, time | A number; time values in the unit the label gives. |
| IP address, port | An IP address, a port number. |
| Check box | On or off. |
| List | One of the values offered. |
The fields start with the protocol's default values. Required parameters have a red *.
Important
Saving new connection parameters does not reconnect the container. Switch the container Off and On again, or restart its communication from the datapoint hierarchy (see Restarting the communication below), so that the new parameters are used.
Hot standby parameters
On a hot standby pair the section Hot Standby communication parameters appears below the connection parameters. The secondary server may need its own connection to the same device (another IP address of the panel, for example):
- Create new Hot Standby communicator adds a second set of the connection fields for the secondary server. The - button next to it (tooltip Delete Hot Standby communicator) removes it when you save.
- Connect only while serving the clients: the secondary server opens this connection only while it serves the clients. Switched off, the connection is kept open all the time.
Footer
- Save stores the container. It is enabled when the name, the handler type and the protocol are set.
- Import metafile: loads the device's datapoint list from a vendor-specific configuration file (see Importing a metafile below). Enabled for a saved container whose handler supports it.
- Browse datapoints: connects to the device and fetches its datapoint list (see Browsing datapoints below). Enabled for a saved container that is switched On and whose handler supports it.
The two import buttons are shown only to users who may import and browse.
Creating a container
- Open File › Settings › Physical structure.
- Click + above Physical Containers. A New container row is added to the list and selected.
- Type the Name. Choose the Handler type, then the Protocol.
- Fill in the Connection fields. The ones marked with
*are required. - On a hot standby pair, if the secondary server reaches the device by other parameters, click Create new Hot Standby communicator and fill in its fields; decide on Connect only while serving the clients.
- Press Save and wait for Saved.
- Switch the container On.
- Load its datapoints with Import metafile or Browse datapoints, or add them by hand with Add child in the tree. Which way works for a device is on its subsystem page.
- Check the container in the datapoint hierarchy and in the main window's warnings: a container that cannot connect is reported there.
Only one new container can be added at a time. Container names do not have to be unique, but distinct names make the trees and the logs easier to read.
Changing the connection parameters
- Select the container in the list, then its own row at the top of the tree.
- Change the fields in the Connection section. Leave a stored password empty to keep it.
- Press Save.
- Switch the container Off, then On again, or restart its communication from the datapoint hierarchy. The server connects with the new parameters.
Deleting a container
- Select the container in the list.
- Click - above the list.
- Confirm the question Do you want to delete the container "..."?.
Warning
Deleting a container deletes all of its datapoints and its hot standby parameters too. A running import or browse of the container is stopped. This cannot be undone.
A new container that was not saved yet is simply removed from the list.
Importing a metafile
A metafile is the configuration export of a panel (its programming software's file). Siwenoid creates, updates and removes the container's datapoints according to it. Which files a handler needs is on its subsystem page.
- Select the saved container and press Import metafile.
- A dialog asks for the files and values the handler needs. For each file, press Open and choose the file (fields marked with
*are required). Fill in the values. - Leave Preview changes ticked and press Save.
- Siwenoid analyses the file (Analyzing metafile...) and opens the Import preview. Nothing has been changed yet.
- Read the preview (see below). Press Import to go on, or Cancel to stop.
- The import runs on the server (Importing metafile). It ends with Metafile import has been finished, or with The metafile import failed. The list shows the new Last updated time.
- If the container was switched on, the client switches it off and on again after the import, so that the server reconnects with the new datapoints.

The import preview: counts, the datapoints that would be created, updated and removed, and the warnings.
The preview shows the File and the Device, the counts New, Updated, Unchanged and Removed, and the lists New datapoints, Updated datapoints and Datapoints to be removed. Warnings tell when the file looks wrong:
| Warning | What to check |
|---|---|
| No metafile was provided. | Choose the file. |
| No datapoints were parsed for this device — wrong file or wrong device address? | The file or the device address given in the dialog. |
| Nothing in the file matched this device — wrong file or wrong device address? | The same. |
| Every existing datapoint would be removed and none created — possibly an older or wrong file. | Do not import: the file is probably of another panel or an old version. |
| More than ... datapoints would be removed; the list is truncated. | Many removals: make sure this is intended. |
Warning
An import also removes the datapoints that are no longer in the file, with their statuses and settings. Read the Datapoints to be removed list before you press Import.
If the handler cannot show a preview, or the analysis failed, you are asked This handler cannot preview the import. Do you want to import anyway? or Could not analyze the metafile. Do you want to import anyway?.
Good to know:
- Always import into the datapoints' own physical container. Datapoints that were moved into logical containers are updated where they are.
- The files of one import may be at most 200 MB together.
- If the client loses track of the job, it says The progress of the server job was lost. The job may still be running: check the result and start it again if needed.
Browsing datapoints
Browsing asks the device itself for its datapoints. The container must be saved and switched On.
- Select the container and press Browse datapoints. The dialog Browsing datapoints shows the progress.
- For most handlers the result is stored at once: Browsing has been finished (or Datapoint browsing error).
- Some handlers, such as ONVIF cameras, let you choose what to import. The dialog Select datapoints to import shows a tree of what the device offers, with a check box for each item:
- colours mark each item as New, Modified, Unchanged or Only in DB (in Siwenoid but no longer on the device),
- Select all and Select none tick or clear every item; for cameras the Name, Stream, User and Password columns are shown too,
- Total sync (delete existing datapoints not in selection) also deletes the existing datapoints you did not tick.
- Untick what you do not want and press Import.
- Confirm import lists the New datapoints, Updated datapoints and Datapoints to delete. Confirm it; the datapoints are saved in the background (Saving datapoints).
Warning
With Total sync ticked, every existing datapoint that is not selected is deleted.
The datapoint tree and its context menu

The context menu of a datapoint in the physical tree.
Right-click a row of the tree:
| Item | Where | What it does |
|---|---|---|
| Add child | Any row (one selected) | Adds a New Datapoint row under the selected one and opens its editor. It is stored when you press Save in the editor. |
| Delete datapoint | Any row except a device (disabled on the System container's own row) | Deletes the selected datapoint, or all selected ones, with all their children, after a question. |
| Delete device only | A device | Deletes only the device; its datapoints are kept. |
| Delete device and all its datapoints | A device | Deletes the device and every datapoint that belongs to it, wherever it is in the tree. |
| Jump to logical hierarchy | Any row | Opens the datapoint hierarchy of the main window at this datapoint. |
| Move back logical moved datapoints | A container row | Every datapoint of that container that was moved into a logical container goes back under its physical parent. There is no question. |
The datapoint editor
Click a datapoint in the tree to open its editor. A new datapoint's editor is titled New datapoint.

The datapoint editor: name and type, and the protocol parameters of a fire panel point.
General tab
Name and type
| Field | Meaning |
|---|---|
| Icon | The datapoint's own icon, chosen from the image library. Right-click it and choose Reset image to go back to the icon of its type. |
| Name | The chosen name. The original name and the datapoint's number are shown under it; the small button next to the original name clears the chosen name, so the original one is used again. |
| Type | The datapoint type, from the types of this handler. The type decides the datapoint's treatments and commands (see Datapoint types, treatments and commands). Not shown for containers. |
Protocol parameters: the addressing of the datapoint in the device (for example a loop and address, a BACnet object or a camera stream). They depend on the handler: see the subsystem pages. Required ones have a red *; passwords behave as in the container editor.
The clients of the System container have the parameters IP Address and MAC Address. If the server's MAC address filtering is on, a client can be used only after its MAC address is entered here and the client is assigned to the user (see Users and groups).
CCTV preset assignments tab
Shown for a saved camera datapoint. It lists the camera's presets, the views an alarm can turn the camera to.

The presets of a camera.
- + under Presets adds a preset, - deletes the selected one (after a question).
- Assignment name: the name shown when the preset is assigned to datapoints.
- Preset identifier: the camera's preset number or token; a new preset starts with
1. Leave it empty for the camera itself, without turning it to a preset.
The presets are saved with the datapoint's Save.
CCTV assignments tab
Shown for every datapoint. It decides which camera opens, and which preset it turns to, when this datapoint raises a status.

The CCTV assignments of a detector: the assigned and the other cameras and presets.
- The list has two groups: Assigned cameras and presets and Other cameras and presets. Type in Search... to narrow it.
- Tick a camera preset to assign it to this datapoint; untick it to remove it. A camera row without a preset means the camera itself, without a preset.
- The changes are stored when you press Save.
How the operators open the cameras: Cameras (CCTV). The camera containers: CCTV cameras (ONVIF, RTSP, Hikvision, Dahua).
Task assignment tab
Shown for the datapoint of a conditional task. Assigned task chooses the conditional command task this datapoint belongs to; leave it empty to clear it. See Tasks.
Saving the datapoint
Press Save under the editor. Save before you select another row: an editor's unsaved changes are dropped when you select another datapoint.
A user who may edit the CCTV assignments but not the datapoints sees Only the CCTV assignments can be saved.; the other fields are disabled. If the datapoint is saved but its CCTV assignments are not, the message The datapoint was saved, but its CCTV assignments could not be: ... tells why.
Map assignments and intervention text assignments are not set here: see Map preferences and the map editor and Intervention texts (setup).
Editing several datapoints at once
Select several datapoints in the tree (Ctrl or Shift click). The editor Multiple selected datapoints opens.

The multi-selection editor's CCTV assignments: a half-ticked row is assigned to only some of the selected datapoints.
- General tab, Common settings: Icon (with Reset image) and, when every selected datapoint has the same type, Type.
- CCTV assignments tab: the same list as for one datapoint. A ticked row is assigned to every selected datapoint, a half-ticked one to only some. Only the rows you change are saved: a row you tick is added to every selected datapoint, a row you untick is removed from every one.
Press Save to apply the changes to all selected datapoints.
Users who may edit the CCTV assignments can also set them on a map: right-click a datapoint button and choose Edit CCTV assignments, or Edit CCTV assignments of the selection for several buttons. That list is saved at once.
Assigning cameras to alarms
- Make sure the camera container is set up and its cameras are imported or browsed (see CCTV cameras (ONVIF, RTSP, Hikvision, Dahua)).
- If a camera should turn to a preset, click the camera datapoint, open CCTV preset assignments, press +, give the Assignment name and the Preset identifier, and press Save.
- Click the datapoint that raises the alarm (or select several), open CCTV assignments, tick the cameras or presets, and press Save.
Restarting the communication
There are two ways to make the server connect to a device again, for example after you changed its connection parameters:
- In Physical structure: switch the container Off, then On. The licence is checked again.
- In the datapoint hierarchy of the main window: right-click the physical container and choose Restart communication. The server disconnects at once and connects again a few seconds later. A container that is switched off cannot be restarted (switch it on instead), and a restart already in progress cannot be started again. Every restart is recorded in the event log.
Permissions
The screen is opened with Manage physical hierarchy. Without further permissions it is read-only. The other permissions of the group, as they are named in Users and groups:
| Permission | What it allows |
|---|---|
| Manage physical hierarchy | Open the screen and see every container and datapoint; Show in physical hierarchy in the datapoint hierarchy. |
| Add / Remove container | The + and - buttons of the container list. |
| Edit container | The General section of the container editor and its Save. |
| Enable / Disable communication | The On / Off switch. |
| Do import / browsing | Import metafile and Browse datapoints (hidden without it). |
| Edit data point | The datapoint editor, the connection parameters of the containers, the task assignment. |
| Create / remove data point | Add child and the delete items of the tree's context menu. |
| Reset container to original hierarchy | Move back logical moved datapoints. |
| Edit CCTV assignments | The CCTV tabs and lists. |
Restarting the communication from the datapoint hierarchy needs Subsystem connection restart. Administrators have every permission.