Sintony SI410
Connecting a Sintony SI410 intrusion panel through a Lantronix XPort serial-to-TCP converter: Sylcom settings, XPort settings, container parameters, browsing the datapoints, commands.
| At a glance | |
|---|---|
| Manufacturer | Siemens (Vanderbilt) |
| Panels | Sintony SI410 |
| Connection | SI400 serial protocol through a Lantronix XPort serial-to-TCP converter |
| Handler type | Sintony SI410 |
| Protocol | Sintony SI400 |
| Datapoints | Browse datapoints |
| Import | none |
Sintony SI410 is an intrusion alarm panel. Siwenoid talks to it with the panel's serial SI400 protocol, through a Lantronix XPort serial-to-TCP converter on the panel's serial connection point. It has not been tested with other converters (for example ATC). Siwenoid does not use the panel's own LAN module. Siwenoid polls the state of the partitions and inputs, and shows the partitions with their rooms, the inputs and the outputs as datapoints. They can be controlled from the datapoint hierarchy, from maps and from the intrusion view.
Siwenoid sets the panel clock when it connects.
Preparing the panel in Sylcom
Use the Sylcom programming software and an SAQ11 programming cable, connected to the J7 connector of the SI410 main board and to the PC.
-
Start Sylcom as administrator, even if your Windows account is an administrator. Log in (no password is needed).
-
Open Management › Product Manager, then Product › Import, and import the product file (.PRO) of the panel. Answer No to every question during the import. An error message here means that Sylcom was not started as administrator.

The Product Manager.
Importing the product file. -
Create a site with Management › New Site, and add the imported product with Search. Ignore any message that the IDs do not match.

A new site. -
Choose Communication › Local › Connect with Initialization, choose the COM port of the cable (the baud rate need not be set) and connect. Then press the INI button on the panel. When the connection is up, upload the configuration from the panel.

Connecting with initialization. -
On the System tab, set:
- Networking mode: the connection point the XPort is wired to (J10 or J1),
- Sending Node: WUD/SFD.

The network settings on the System tab. -
If the XPort is on J10, set the Serial Port protocol to No Protocol on the ARC tab. On J1 nothing else is needed.

No protocol on the serial port (J10 only). -
Send the configuration to the panel.
Preparing the XPort
- Set the XPort's serial port to:
- RS-232,
- 9600 baud,
- 8 data bits,
- no parity,
- 1 stop bit,
- no flow control.
- Give the XPort a fixed IP address, and note the TCP port on which it accepts the connection. Siwenoid connects to this address and port.
- In the XPort's connection settings, set the server (remote host) IP address to
0.0.0.0. Without it the connection does not work properly.
Creating the container
Create the container in Preferences › Physical structure (see Physical structure for the editor in general). Give it a name, choose Sintony SI410 as Handler type and Sintony SI400 as Protocol, then fill in the connection parameters.

The container editor with the Sintony connection parameters.
| Field | Meaning | Default |
|---|---|---|
| Host IP | IP address of the XPort. Required. | |
| Port | TCP port of the XPort. Required. | |
| User ID | ID of the user created for the monitoring in the panel. Siwenoid sends the commands and the clock setting with this ID. Not necessarily 3: look it up in the panel programming. If left empty, 3 is used. |
Save the container and switch its connection on.
Getting the datapoints
Sintony has no configuration file to import: Siwenoid reads the datapoints from the panel.
-
Wait until the container is connected. Browse datapoints works only while the container is online.
-
Press Browse datapoints. Siwenoid reads the panel and builds the hierarchy with these folders, the elements named as programmed in the panel:
- Inputs,
- Outputs,
- Wards (the partitions, with their rooms),
- System.
An element without a name gets a generic one, for example "Input #5". These names follow the language of the operator who browses.
-
In Select datapoints to import, untick what you do not need and press Import.
The datapoint editor shows what browsing read from the panel; leave these as they are:
- Device number,
- PCX number,
- Device kind,
- Device type,
- Device subtype,
- Partition link.
Siwenoid watches the inputs that exist as datapoints.
Treatments and commands
The treatment file of the Sintony SI410 (si410.trt, in the TreatmentTables folder of the Siwenoid server) comes with the handler, and the server loads it by itself at its first start. Before you switch on the first container, check in Preferences › Datapoint types that the handler's types have treatments. If they have none, or you received an updated treatment file, import the file by hand (see Importing a treatment file); without treatments the panel's signals do not appear and there are no commands. The main commands:
| Datapoint | Commands |
|---|---|
| Partition | Full set, Part set, Unset, Clear alarm, Reset sounders/bells |
| Room | Full set, Unset |
| Input | Bypass, Unbypass, Activation pulse, Clear alarm, Reset sounders/bells |
| Output | Start test mode, End test mode, Toggle output |
| System | Set A/V zone to Autoswitch |
The input's soak test and activation latch commands, the system's transmission to CMS1 / CMS2 on and off, and the choice of a fixed A/V zone also exist. If a command does not appear in the signal log, on maps or in the intrusion view, switch on its Shown in the interface option in Preferences › Datapoint types (see Datapoint types, treatments and commands).
Checking the connection
- The panel datapoint shows connected in the datapoint hierarchy.
- Activate an input, and check that its state changes in Siwenoid.
- If the container does not connect, check the XPort's address and port, and that the server IP address in the XPort is
0.0.0.0. - If it connects but nothing arrives, check:
- the XPort's serial settings,
- the wiring,
- the connection point (J1 or J10) and, on J10, the No Protocol setting on the ARC tab,
- that the handler's types have treatments (Preferences › Datapoint types).