Signal log
The signal log lists the active alarms and signals: its rows and buttons, acknowledging, removing, commands, forced action forms, notes, sounds, popups, user messages, filters, offline mode, export and print.
The signal log is the first tab of the main window and the operator's most important screen. It lists every active state of the connected systems that needs attention: alarms, faults, disablements and other signals. A site at rest shows an empty signal log with the text There is not any event to show.
Every user has the signal log; it cannot be closed or hidden. Which rows you see depends on your user: rows of parts of the site that your administrator has not given you access to are not shown.
What appears in the signal log
When a device reports a state that is not normal, Siwenoid adds a row. The row's colour is the colour of its treatment category; the same colour is used on the category strip, on maps, in the datapoint hierarchy and in the event log.
The engineer decides which treatments appear here: some states are shown only on maps, and categories with priority 0 never appear in the signal log.

The signal log with new, acknowledged and removed rows in several categories.
The three states of a row
| State | Meaning | Look |
|---|---|---|
| NEW | The state is active and nobody has acknowledged it yet. | Category colour, bold text. The row's icon may blink, the chip on the category strip blinks and the alarm sound plays. |
| ACKNOWLEDGED | The state is still active and an operator has acknowledged it. | Steady colour, normal text. |
| REMOVED | The device has returned to normal, but nobody acknowledged the row before that. | The colour fades through black. It blinks like a new row. One click clears it. |
An unacknowledged alarm never disappears just because the device returned to normal: it stays as REMOVED until an operator clears it, so a short alarm is never missed. An acknowledged row disappears when the device returns to normal, unless your site is set to keep such rows as REMOVED too.
Some treatments are acknowledged automatically: their rows arrive already acknowledged. A small lock on a datapoint's icon means that the datapoint is locked; only administrators can send commands to it.
Parts of a row

One row with all its buttons.
From left to right:
| Part | What it shows and does | If you do not see it |
|---|---|---|
| Category icon | The icon of the treatment category. | |
| Time | The time (HH:mm:ss) with the date (yyyy.MM.dd) under it, by the server's clock. |
|
| Datapoint | The datapoint's icon and name, with its technical text in a small tag. A long name is shortened at the start, so the end of the name stays visible. Under it: the name of the physical container (for example the fire panel). | |
| Treatment | The name of the state, for example Fire alarm or Fault, on the right side of the row. | |
| Command button | Sends the default command or opens the command menu (see Commands). | Your administrator has not given you access to sending commands. |
| Map button | Active when the datapoint is on a map you may see; its tooltip lists the maps. Click it to open the first map with the datapoint highlighted (see Maps). Grey when the datapoint is on no map. | Your administrator has not given you access to maps. |
| Intervention text button | Active when instructions are assigned to the datapoint; its tooltip lists them. Click it to open them (see Intervention texts). | Your administrator has not given you access to it. |
| Note button | Shows whether the alarm has notes; its tooltip shows the latest one. Click it to read and write notes (see Notes). | Your administrator has not given you access to notes. |
| Show in datapoint hierarchy | Selects the datapoint in the tree and brings the Datapoint Hierarchy tab to the front. | Your administrator has not given you access to the datapoint hierarchy. |
Hovering a row outlines it. The mouse wheel scrolls the list one row at a time.
Acknowledging
Acknowledging tells Siwenoid that you have seen the alarm. It stops the row's blinking and, if nothing else is waiting, the sound. It sends nothing to the fire panel or the intrusion panel: to act on a device, use a command.
- Read the row: time, container, datapoint and treatment.
- Click the row (the time, name or treatment area). The tooltip says Acknowledge.
- The row turns steady and its text normal. If a form opens under the row instead, fill it in first (see Forced action forms).
To acknowledge all new rows of a category at once, use the chip's Ack button, its F key, or Ctrl+F12 for everything (see Category strip).
Whether your acknowledgement also counts on other workstations is a setting of your site:
| Site setting | Effect |
|---|---|
| Acknowledge by clients | Each workstation acknowledges separately. |
| User synchronized acknowledge | An acknowledgement counts on every workstation where the same user is logged in. |
| Synchronized acknowledge | An acknowledgement counts on every workstation. |
Ask your engineer which one your site uses. The site can also record every acknowledgement in the event log with your name.
Removing a row
A REMOVED row is an alarm that ended before anyone acknowledged it. Read what it was, then click it once (the tooltip says Remove) to clear it from the list.
Some treatments can be removed by the operator while they are still active. Such a row shows a remove icon in place of the command button, with the tooltip Remove Status; click it to remove the status.
Commands
The command button sends a command to the device, for example to silence the sounders or reset the panel.
- Left click: sends the row's default command; its name is the button's tooltip. If the row is new or removed, the same click also acknowledges it.
- When the row has no default command, or you may not send default commands, the button shows a neutral icon and a left click opens the command menu instead.
- Right click: always opens the command menu, the list of the datapoint's commands with their icons. Click a command to send it.
- A grey, inactive button means that the datapoint has no command for you, or it belongs to a part of the site you may not control.

The command menu opened with a right click on the command button.
A command is sent at once. Some commands need your passcode: the Passcode required window shows the Command and the Data point(s) and asks Enter your 4-digit passcode to send this command:. After too many wrong passcodes you have to wait a few minutes before trying again. A command that fails is reported in a Sending commands window with the reason.
Forced action forms
For some alarms the engineer defines a form that must be filled in before the alarm can be acknowledged (see Forced actions). For such an alarm:
- Click the row. A Forced actions pane opens under the row, in the row's colour. The row stays NEW but no longer drives the alarm sound.
- Fill in the fields. A field can be a text field (enter text), a single choice (choose one) or a multiple choice (select multiple). Required fields are marked with a red
*. - Click Save. A missing required field is outlined in red and Fill in the required fields (marked with
*). appears. - Click the row again: now it is acknowledged. The filled form stays under the row, collapsed and read-only.
On some sites the form is stricter: the alarm keeps sounding until the form is saved.

A forced action form under an alarm row.
| Message under the form | What to do |
|---|---|
| The forced actions were changed meanwhile; fill in the new form. | The engineer changed the form. Fill in the new one. |
| The forced action forms were edited meanwhile; the answers typed so far were discarded, fill in the new form. | As above; your answers were lost. |
| The signal log is being reloaded from the server; save again once it is back. | Wait a moment, then click Save again. |
The Forced Actions tab
Where the workstation is set up for it, + › Forced Actions opens a tab that lists every status whose form is still to be filled in. Use it to fill in the same form for several alarms at once:
- Choose a category at the top, or ALL.
- Select the statuses in the list (Select all, Clear selection). They must have the same form, otherwise the tab says Selection is invalid.
- Fill in the form and click Save selected.
An empty list says There is no status with missing forced action to show.
Notes
A note documents what happened and what was done. Notes are kept with the alarm, every operator sees them, and they are also written to the event log.
- Click the row's note button. The Notes window lists the notes with date, user and text (No notes yet. when there are none).
- Type into New note (What happened, what was done). Enter sends; Shift+Enter starts a new line.
- Click Send.
Notes cannot be edited or deleted afterwards. When several alarms are selected on a map, the same window shows The notes of N statuses; a new note goes to each of them. and the button Send to all.

The Notes window of an alarm.
For something that has no alarm row, write a free note: toolbar Note › Add note, type the Note and click Send. It goes into the event log with the current time.
If you can read notes but cannot write them, or do not see the note button, your administrator has not given you access to it.
Sounds and popups
The sound of the most important category that has a new or removed row plays in a loop. When those rows are acknowledged or cleared, the sound of the next category with waiting rows plays, or the sound stops. A row whose forced action form is open does not drive the sound.
To silence the sound:
- click Mute on the toolbar or press F12: this stops the current sound only; the next change in the signal log can start it again;
- acknowledge the rows.
The alert sound of connection warnings and alert notes takes precedence over the category sounds (see The main window).
The sounds of a workstation are set in File › Settings › Sound: Enable sounds, and per category Mute, Loop, Preview and the volume, with a Master volume. These settings belong to the computer, not to the user.
A category or treatment can be set to bring the client window to front: when such an alarm arrives, a minimised client window is restored and comes to the front.
The toolbar
The toolbar runs down the right edge of the signal log. Hover it to see the buttons' names.

The toolbar with the button names shown.
| Button | What it does |
|---|---|
| Online / Offline | Pauses the list so that rows do not move while you read them (see Offline mode). |
| Mute | Silences the current sound, like F12. |
| Sort | Chooses the order of the rows. |
| Filter | Hides the rows of chosen containers and devices on this workstation. |
| Types | Switches the type and category filter of this workstation on or off. |
| Export | Saves the rows shown to an XLSX file. |
| Prints the rows shown. | |
| Note | Add note: a free note to the event log. Administrators also get Send an alert note. |
| Message | Opens the user messages (see User messages). |
If a button is missing, your administrator has not given you access to it. The Types button appears only on workstations where the engineer has set up a type and category filter.
Offline mode
- Click Online and choose Offline mode.
- The button turns amber. Its tooltip tells when the list goes live again: Offline: the signal log is paused; it goes online again at …
- After one minute the list returns to online by itself and catches up. To return earlier, choose Online mode.
Only the list pauses. The category strip, the counters, the sounds and the popups keep working while it is offline.
Sorting
Sort offers four orders. Your choice is remembered on this computer.
| Order | Rows |
|---|---|
| Sort by categories from top (default) | The most important category on top, the newest first within a category. |
| Sort by categories from bottom | The same, filled from the bottom of the list. |
| Sort by time newest on top | Newest row on top, whatever its category. |
| Sort by time newest at bottom | Newest row at the bottom. |
Container filter
Filter opens Containers shown: a tree of the physical containers and their devices. Untick a container or device to hide its rows (The signal log shows the signals of the ticked containers and devices only.). Tick all and Untick all help. While anything is hidden, the button is marked and its tooltip says Container filter on: some containers are hidden.

The container filter with one container unticked.
The filter applies to this workstation only; other operators still see the rows.
Warning
Hidden rows still exist. Turn the filter off when you no longer need it, so that you do not miss alarms.
Type and category filter
The engineer can set up, per workstation, rules for types of datapoints and categories to leave out (for example the disablements of one system). Types switches these rules on or off with one click. While on, the matching rows are hidden from the signal log, the counters and the sound; maps and the datapoint hierarchy still show them.
Export and print
- Export › Export signal log to XLSX file saves the rows currently shown: date, time, physical container, datapoint with technical text, treatment and state (NEW, ACKNOWLEDGED, REMOVED), coloured like the list. The proposed file name contains the date and time. Progress and result appear as notice cards.
- Print prints the rows currently shown. Each page has the title … signal log, the time of printing and a page number.
User messages
User messages are short notes between operators, for example for the next shift. They appear in the signal log's message panel of every operator.
To read the messages, click Message on the toolbar. The User messages panel opens under the list, with the number of unread messages. While unread messages exist, the Message button has an amber background.
| Column | Content |
|---|---|
| Message send date & time | When it was sent. |
| Sender | Who sent it. |
| Datapoint | The datapoint it mentions, if any. Click it to show the datapoint in the tree. |
| Message | The text. |
| Acknowledge message | Marks it read or unread on this workstation. |
| Remove message | Deletes the message. Only its sender or an administrator can do this. |
To send a message:
- Click New message in the panel (or right-click Message and choose Send user message).
- Type the Message. To mention a datapoint, drag it from the datapoint hierarchy into Datapoint (optional).
- Click Send.
Double-click a message to send it again as a new one. When another operator's message arrives, a New user message card appears with Open, and the Message button bounces. Your own messages do not alert you.

The user messages panel under the signal log.
If you cannot send messages, your administrator has not given you access to it.
Alert notes
Administrators can send an alert note to every logged-in operator: toolbar Note › Send an alert note. Every operator gets it as an Alert message card with the alert sound, and it is recorded in the event log. Close the card to stop the sound.
When a change is refused
If an acknowledgement, a removal or a note cannot be carried out, a Status not changed card tells why:
| Message | Meaning |
|---|---|
| You do not have the permission for this. | Your user may not do this. |
| The status no longer exists or is not visible to you. | Someone else cleared it, or it is outside your area. |
| This status cannot be removed. | Its treatment is not removable. |
| The signal log has been reloaded from the server. Please try again. | Try again. |
| The server could not be reached. Please try again. | The connection is down; see the warning list. |
| The server did not answer; the change may have been carried out anyway. | Check the row before trying again. |
After a connection loss, the signal log is rebuilt from the server's state when the connection is back.