A walkthrough of an operator's shift: starting it, handling an alarm from the first sound to the note, handling many alarms, typical situations and the hand-over.

This page follows an operator through a shift: logging in and checking the system, handling an alarm from the first sound to the last note, dealing with many alarms, and handing over to the next shift. Each step links the page that describes the screen in detail.

The examples use a fire alarm on a smoke detector. Your screens may have fewer buttons than the pictures: Siwenoid shows each user only what their administrator has given them access to.

Six things to keep in mind

  1. Acknowledging is not resetting. Clicking an alarm row, or a category's Ack button, tells Siwenoid "I have seen it": the blinking and the sound stop. Nothing is sent to the fire or intrusion panel. To act on a device, send a command.
  2. A row has three states: NEW (bold, blinking), ACKNOWLEDGED (steady) and REMOVED (fading through black: the condition has ended, but nobody acknowledged it; one click clears it). See Signal log.
  3. The colours are the same everywhere: a category has one colour on the category strip, in the signal log, on the maps, in the datapoint hierarchy and in the event log.
  4. What you see depends on your user: a colleague may have more or fewer buttons and see other parts of the site.
  5. Everything is recorded in the event log with your name: commands, notes, logins and, if your site records them, acknowledgements.
  6. The sound belongs to the most important waiting category. It plays until the rows are acknowledged. F12 or Mute only silence it for now.

Starting the shift

  1. Log in. Type your username and password, or, if the previous operator is still logged in, choose File › Switch User and log in there (see The main window). Your saved layout comes back: your pinned tabs and workspace windows.
  2. Check the connection. The connection icon next to the server time is green and the warning list at the bottom of the window is empty. A red icon, or a warning such as No connection to the server: new alarms do not arrive., means you may not see new alarms: tell the engineer or your supervisor at once and follow the site's backup procedure. The check button of the warning row silences its alert sound; the row stays until the problem is fixed.
  3. Read the signal log from the top. With the default order the most important category is on top. Rows left from the previous shift are still there: faults and disablements stay as ACKNOWLEDGED rows while they last. Hover their note button to read why they are there.
  4. Read the hand-over. Click Message on the signal log toolbar to read the user messages of the previous shift. If needed, open the event log and look at the last hours (the period mode Last … Hour(s), see Event log).
  5. Check the category strip. A blinking chip means that something waits. 0 / 5 means five rows exist and all are acknowledged (see Category strip).
  6. Check the sound and the printer. Make sure the workstation's sound is on (File › Settings › Sound) and that a printer is available where the site prints alarms.

The main window at the start of a quiet shift: green connection icon, no warnings, only acknowledged fault rows.
The main window at the start of a quiet shift: green connection icon, no warnings, only acknowledged fault rows.

Handling an alarm

A smoke detector goes into alarm. The ALARM chip blinks, a bold red row appears at the top of the signal log and the alarm sound plays.

A new fire alarm: the blinking chip and the new row at the top of the signal log.
A new fire alarm: the blinking chip and the new row at the top of the signal log.

  1. Read the row. The time tells when, the container which panel, the datapoint name and technical text which detector, the treatment what happened. To silence the sound while you read, press F12.

  2. Open the instructions. Click the row's intervention text button to read what to do (see Intervention texts). On some sites the instructions open by themselves.

    The intervention text of the alarm opened beside the signal log.
    The intervention text of the alarm opened beside the signal log.

  3. Find the place. Click the map button: the map opens with the detector highlighted (see Maps). The Show in datapoint hierarchy button shows it in the tree instead (see Datapoint hierarchy). If the site has cameras, open the live picture from the map button's right-click menu (Show live video, see Cameras (CCTV)).

    The map with the alarming detector highlighted.
    The map with the alarming detector highlighted.

  4. Acknowledge. Click the row. If a forced action form opens under the row, fill in the required fields (marked with *), click Save, then click the row again. Where the site requires a form, the alarm cannot be acknowledged without it (see Signal log).

    The forced action form under the alarm row.
    The forced action form under the alarm row.

  5. Act. Follow the instructions and the site procedure: call the responsible person, and send a command only when the procedure says so. Click the command button for the default command, or right-click it for the list of commands; type your passcode if asked. Check the result: the row or the map icon changes when the device reports its new state. A failed command is reported in a Sending commands window.

  6. Document. Click the row's note button and write what happened and what was done. The note stays with the alarm for every operator and goes into the event log.

  7. Wait for the device to return to normal. An acknowledged row then disappears. A row nobody acknowledged turns REMOVED: read it, then click it once to clear it.

    An alarm that ended before it was acknowledged: the removed row.
    An alarm that ended before it was acknowledged: the removed row.

  8. Close the loop. If the next shift has to follow up, send a user message: Message › New message, with the detector dragged from the tree into Datapoint (optional).

Handling many alarms

Typical situations

Situation What to do
Fire alarm Acknowledge, read the intervention text, check the map and the cameras, follow the site procedure. Send commands (for example silencing the sounders, or a reset after the all-clear) only as the procedure says. Write a note.
Fault or disablement rows Acknowledge them; they stay while active. Add a note with the reason. Do not hide their category without a reason: other events of the same category would be hidden too.
Intrusion + › Intrusion › Area & Zone states shows every area and zone; arm, disarm and reset from there (see Intrusion view).
A detector must be switched off for maintenance Send the panel's disable command for it, as the site procedure says, and note the reason and the technician's name.
No connection to the server The alert sound plays and a red card says that the client reaches no server. Tell the engineer at once. With a redundant server pair the client moves to the other server by itself.
A panel reports lost communication The alarm is real: the system has lost the panel. Follow its intervention text and tell the engineer.
An Alert message card arrives Read it; closing the card stops the sound.
A New user message card arrives Click Open and read the message.
You need the history of one detector Events (24h) in the datapoint hierarchy's information pane, or the event log filtered for it (see Event log).
You need a paper copy Print on the signal log, the event log, a map or an intervention text.

Warning

A simulated alarm is a real alarm for every operator. Simulate only for tests, with your supervisor's knowledge.

Ending the shift and handing over

  1. Leave no unread alarms behind. Acknowledge what you have handled and clear the REMOVED rows after reading them.
  2. Write the hand-over. Send a user message to the next operator, and add notes to the alarms that are still open. If your site requires it, export or print the signal log (toolbar Export or Print).
  3. Hand over the workstation. Choose File › Switch User and let the next operator log in, or choose File › Logout. Never leave the client unattended while you are logged in.

The hand-over: a user message for the next shift and File › Switch User.
The hand-over: a user message for the next shift and File › Switch User.

A sample shift

Time What the operator does See
06:00 Logs in, checks the connection icon and the warning list, reads the night's rows and messages. The main window, Signal log
06:10 Reads the notes of the night's fault rows. Signal log
08:42 A smoke detector alarm: reads the row and the intervention text, checks the map and the camera, fills in the form, acknowledges, sends the reset after the check, writes a note. Handling an alarm
09:15 A technician asks for a zone to be disabled: sends the disable command and notes the reason and the technician. Datapoint hierarchy
11:30 Prepares a report: event log for the last 24 hours, exported to XLSX. Event log
13:55 A connection warning: tells the engineer and follows the backup procedure. The main window
14:00 Hand-over: a user message, then File › Switch User. Ending the shift