Siwenoid Wiki

Generic Modbus TCP

Reading device states from a PLC's holding registers over Modbus TCP, for project-specific integrations set up by hand.

At a glance
Device a PLC or gateway that publishes states in holding registers
Connection Modbus TCP
Default port 502
Handler type Modbus-Unsupported
Protocol Modbus/TCP
Datapoints created by hand
Import none
Treatments created by hand
Commands none

The generic Modbus handler reads holding registers of a PLC or gateway over Modbus TCP and turns the register values into datapoint states. It is meant for project-specific integrations: the PLC programmer and the Siwenoid engineer agree on a register table, and the datapoints and treatments are set up by hand. It is not a ready-made driver for a particular device, which is why it is listed as Modbus-Unsupported in the Handler type list. It only monitors: no commands are sent to the PLC.

What you need from the PLC programmer

A register table that lists:

Holding register numbers are entered without the leading 4: register 40101 is entered as 101.

Creating the container

Create the container in Preferences › Physical structure (see Physical structure for the editor in general). Choose Modbus-Unsupported as Handler type and Modbus/TCP as Protocol.

Field Meaning Default
Host IP IP address of the PLC. Required.
Port Modbus TCP port of the PLC, usually 502. Required.

The container editor with the Modbus/TCP connection parameters.
The container editor with the Modbus/TCP connection parameters.

Save the container. The datapoints go into two containers under it: a physical one for the register ranges and a logical one for the devices. Siwenoid may have created them already; if not, add them with Add child, one of type TYPE_PHYSICAL_CONTAINER and one of type TYPE_LOGICAL_CONTAINER.

Adding the register range and the devices

  1. Under the physical container, add a datapoint of type TYPE_PHYSICAL_DATAPOINT for the register range. Enter the first register in Address Low and the last one in Address High. Siwenoid reads every register in this range, both ends included. Add more such datapoints for further ranges.

    The register range: Address Low and Address High.
    The register range: Address Low and Address High.

  2. Under the logical container, add a datapoint of type TYPE_HOLDING_REGISTER for every device in the table. Give it the device's name, and enter the device's register number both in Address and in Modbus Number. The register must lie inside a range from step 1.

    A device datapoint: the same register number in Address and Modbus Number.
    A device datapoint: the same register number in Address and Modbus Number.

Example for registers 40101 to 40110, with a device on register 40105:

Other encodings, such as single bits of a register, are possible; agree them with Siwenoid support.

Treatments

The handler comes with no default treatments and no treatment file: create every treatment by hand before you switch the connection on. In Preferences › Datapoint types, select the Modbus-Unsupported handler and the TYPE_HOLDING_REGISTER type, and add a treatment for every value in the register table (see Creating and deleting treatments):

Give every treatment of the handler a different State value. A value with no matching treatment changes nothing.

Warning

Do not use Import treatments for this handler. The import deletes the treatments created by hand on the handler's types and creates none.

Checking the connection

  1. Switch the container On with the toggle at the top of the editor.
  2. Change a register on the PLC (or ask the PLC programmer to) and watch the device's datapoint in the datapoint hierarchy.
  3. If nothing changes, check the IP address and port, that the register lies inside a range, and that a treatment exists for the value.