INIM Previdia Max
Connecting an INIM Previdia Max fire panel over Modbus TCP, directly or through a serial converter: panel settings, container parameters, importing the PREVIDIA-STUDIO database.
| At a glance | |
|---|---|
| Manufacturer | INIM |
| Panels | Previdia Max |
| Connection | Modbus TCP (Ethernet), or Modbus RTU through an RS-232 to TCP/IP converter |
| Default port | 502 (direct Ethernet) |
| Handler type | INIM Previdia Max |
| Protocol | INIM Previdia Max Modbus over TCP/IP |
| Import | PREVIDIA-STUDIO database (.mdb, .bdk) |
The INIM Previdia Max is an addressable fire panel. Siwenoid reads its state over Modbus and shows the panel, its loops, loop devices, modules, zones and groups as datapoints. Operators can switch the panel between day and night mode, silence it, reset it, and enable or disable zones, devices and outputs.
The panel connects either directly over Ethernet (Modbus TCP) or through an RS-232 to TCP/IP converter (Modbus RTU over TCP). The datapoints come from the panel's configuration in PREVIDIA-STUDIO, the panel's programming software.
Preparing the panel
Do these steps in PREVIDIA-STUDIO.
-
Go to the PANEL DISPLAY section of the panel.
-
Make sure the option Modbus Tcp Disabled is set to Off.

PREVIDIA-STUDIO: the Modbus TCP option and the MODBUS Address edit sign at the bottom. -
Click the edit sign next to MODBUS Address and choose the panel's Modbus address. Enter the same address in Siwenoid.

Choosing the panel's Modbus address. -
Download (write) the changes to the panel.

Writing the configuration to the panel.
If you use an RS-232 to TCP/IP converter, set its TCP server serial settings:
| Setting | Value |
|---|---|
| Bit rate | 115200 bit/s |
| Data bits | 8 |
| Parity | even |
| Stop bits | 1 |
| Hardware flow control | none |
Creating the container
Create the container in Preferences › Physical structure (see Physical structure for the editor in general). Set:
- Handler type: INIM Previdia Max
- Protocol: INIM Previdia Max Modbus over TCP/IP
Then fill in the connection parameters.

The container editor with the INIM Previdia Max connection parameters.
| Field | Meaning | Default |
|---|---|---|
| Host IP | IP address or host name of the panel, or of the converter. Required. | |
| Port | 502 for a direct Ethernet connection; with a converter, the port of the converter's TCP server. Required. |
|
| Modbus address | The panel's Modbus address set in PREVIDIA-STUDIO, from 0 to 255. Required. | |
| Modbus RTU | Off for a direct Ethernet connection, on with an RS-232 to TCP/IP converter. | off |
Save the container.
Importing the datapoints
The datapoints come from the PREVIDIA-STUDIO database. You need one of these files on the computer running the Siwenoid client:
DB.mdb, in theDatafolder of the PREVIDIA-STUDIO installation (by default underC:\Program Files (x86)\PREVIDIA), or- a PREVIDIA-STUDIO database backup (
.bdk).
You also need two numbers from PREVIDIA-STUDIO: the ID of the Solution that holds this panel's configuration (usually 1) and the ID of the Cluster the panel belongs to (usually 0, unless several clusters are defined).

Finding the Solution and Cluster IDs in PREVIDIA-STUDIO (1/4).

Finding the Solution and Cluster IDs in PREVIDIA-STUDIO (2/4).

Finding the Solution and Cluster IDs in PREVIDIA-STUDIO (3/4).

Finding the Solution and Cluster IDs in PREVIDIA-STUDIO (4/4).
-
Select the container and press Import metafile.
-
Choose the database file with Open: the
.mdbfile in the Previdia Studio Database row, or the.bdkfile in the Previdia Studio Database Backup row. -
Fill in the IDs:
- Client ID: the Solution ID,
- Cluster ID: the Cluster ID.
-
Leave Preview changes ticked and press Save.

The metafile import of an INIM Previdia Max container. -
Read the Import preview: the numbers of new, updated, unchanged and removed datapoints, and the warnings. Press Import.
-
Wait for Metafile import has been finished.
The import creates the panel with its power supply, loop, relay, I/O and extinguishing modules, the loops and their devices, and the zones and groups. Each loop device is placed under its zone.
Switch the container On with the toggle at the top of the editor.
Treatments and commands
The INIM Previdia Max treatment file (previdiamax.trt, in the TreatmentTables folder of the Siwenoid server) comes with the handler, and the server loads it by itself at its first start. Before you switch the container on, check in Preferences › Datapoint types that the handler's types have treatments. If they have none, or you received an updated treatment file, import the file by hand (see Importing a treatment file).
The file defines the panel's treatments (alarm, early warning, fault, disabled, day and night mode, test, the extinguishing treatments and more) and these commands (see Datapoint types, treatments and commands to change them):
| Datapoint | Commands |
|---|---|
| The panel (SYSTEM) | Day mode, Night mode, Silence buzzer, Mute, Unmute, Investigate, End pre-alarm, Rearm, Action 1-5 |
| Outputs and I/O channels | Enable, Disable, Activate, Deactivate |
| Loop devices and modules | Enable, Disable |
| Zones | Enable, Disable, Perform test, End test |
Checking the connection
-
Watch the datapoints in the datapoint hierarchy: their states follow the panel.
-
Disable a zone from Siwenoid and check it on the panel, then enable it again.
-
If the container does not connect, check:
- the IP address and port,
- the Modbus RTU setting (off for direct Ethernet),
- that Modbus Tcp Disabled is Off on the panel,
- that the Modbus address matches the panel's.
-
If the import preview warns that nothing matched, check the database file and the Client and Cluster IDs.